Model NO.: HLLA-03SI~45TI
Application Fields: Printing
Application Machine: Combination machine
Certification: CE
Condition: New
Cooling Capacity: 9.2kw-142.2kw
Refrigerant: R22, R407c
Power Supply: 380V-3-pH-50Hz
Evaporator: Shell and Tube Type
Function: Direct Cooling
Cooling Range: 20~40 Degree
Chilled Water Flow: 26.4~408.3L/M
Dimension: 3200*1180*2200
Weight: 130~1280kg
Trademark: Golden
Specification: CE
Origin: Dongguan, Guangdong
HS Code: 8418692090
Mould injection air cooled water chiller1. The chiller adopt high-quality compressor and Italy pump, so it is very sate and noiseless, economical in power and durable
2. The chiller is deployed with Italy temperature controller, it can control the temperature between 3 and 35 degrees exactly
3. The designs of chiller and radiator are unique, so the heat exchange efficiency is very high
4. The chiller is designed to be with current over-load protector, high voltage and low voltage construction and electric time-delay safeguard, when malfunction happened, it could alarm and show the cause of the problem in time.
5. It has stainless steel temperature-holder box, it is very convince to purify
6. It is designed to be with anti-phase & lack-phase protector and anti-icy protector
7. The temperature of ultra cod chiller can be below -15 degrees.
8. This series chiller can customize base on the requirement of acid resistant & acidity-resistant
9. It has got CE certification.
                                        Industrial Air Cooled Chiller | |||||||||||||
 Model HLLA ~ | 03SI | 05SI | 08SI | 10SI | 12.5SI | 15SI | 20DI | 25DI | 30DI | 40TI | 45TI | ||
Rated Cooling Capacity | ×1000 kcal/h | 7.9 | 12.8 | 20.8 | 27.9 | 32.3 | 40.8 | 55.7 | 64.7 | 81.5 | 97.0 | 122.3 | |
KW | 9.2 | 14.9 | 24.2 | 32.4 | 37.6 | 47.4 | 64.8 | 75.2 | 94.8 | 112.8 | 142.2 | ||
Input Power (KW) | 3.85 | 5.55 | 8.15 | 10.4 | 12.0 | 16.0 | 20.1 | 22.5 | 31.2 | 33.7 | 45.7 | ||
Comp. Input Power×Qty. (KW) | 2.6 | 4.3 | 6.35 | 8.1 | 9.3 | 12.5 | 8.1×2 | 9.3×2 | 12.5×2 | 9.3×3 | 12.5×3 | ||
 Chillded Water Pump Model | HT1.0DK-20 | HT1.0DK-20 | HT40-15 | HT40-15 | HT50-17 | HT50-17 | HT50-17 | HT50-17 | HT65-19 | HT65-19 | HT65-19 | ||
 Chilled Water Pump Power (KW) | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.5 | 1.5 | 1.5 | 2.2 | 2.2 | 2.2 | ||
 Comp. Current (A) | 6.8 | 10.5 | 14 | 17.5 | 20 | 25.6 | 33.8 | 37.2 | 49.8 | 55.8 | 72.6 | ||
Power Supply | 3φ-380V-50HZ | ||||||||||||
 Safety Protection | Phase reversion protection, Phase lack protection, Overload current protection, Discharge air temp. protection, Low & High pressure protection, Low temp. protection, Water flow protection, |
||||||||||||
 Number of Refrigeration Circuit | 1 | 2 | 3 | ||||||||||
 Capacity Control (%) | 0, 100 | 0, 50, 100 | 0, 33, 66, 100 | ||||||||||
 Refrigerant | R22 | ||||||||||||
 Condenser | Ripple Aluminum Fins around Cooper Pipe | ||||||||||||
 Power lnput of Fan (KW) | 0.5 | 0.5 | 0.7 | 1.2 | 1.2 | 2.0 | 2.4 | 2.4 | 4.0 | 3.6 | 6.0 | ||
 Evaporator | Pipe Coil Type |  Shell and Tube Type | |||||||||||
 Water Side Max Pressure (MPa) | - | 1 | |||||||||||
 Dia.of Pipe to Evaporator (inch) | 1" | 1-1/2" | 2" | 2-1/2" | |||||||||
 Chilled Water Flow (L/m) | 26.4 | 42.7 | 69.4 | 92.9 | 107.8 | 135.9 | 172.0 | 194.8 | 272.2 | 292.2 | 408.3 | ||
 Evaporator Water Pressure drop (kPa) | - | 17 | 23 | 28 | 30 | 28 | 28 | 32 | 32 | 31 | |||
 Running Noise dB(A) | 72 | 72 | 73 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | ||
 Tank Volume (L) | 80 | 80 | 180 | 180 | 180 | 180 | 270 | 270 | 270 | 270 | 270 | ||
 Total weight (Kg) | 130 | 170 | 430 | 480 | 510 | 560 | 840 | 880 | 980 | 1130 | 1280 | ||
 Dimension L×W×H | 1000×650×1500 | 1500×1100×2200 | 1500×1180×2200 | 2200×1180×2200 | 3200×1180×2200 |
ATS Auto Parts Manufacturing Co., Ltd. , http://www.sd-autoparts.com