Lubrication oil pump outlet pressure is low from the start switch PSXL-08404 0.6MPa setting value, the switching operation of two pressure very close, so that the lubricating oil pump outlet pressure when the switching operation has little hysteresis, it may cause first carbon dioxide compressor jumping, and then start Oil auxiliary pump.
Shorting through the instrument switch, disconnect the experiment, auxiliary pump since the start of a good condition. Through the entire system even school, found that the pump outlet pressure is low when the pressure switch slow. Check the switch did not find abnormal switching. Lubrication pump outlet pressure low Interlock switch take pressure point In the pump outlet, the pressure switch installed in the switchgear, away from the pressure point between the pressure guide tube length of about 8m, and guide tube diameter smaller. When the oil pump outlet pressure is low, due to large pressure guide tube resistance, the measuring element can not be timely pressure relief, resulting in slow switching, the reaction lag, resulting in low oil pressure control interlock switch PSXL-08301, so that the carbon dioxide compressor trip .
From the switching settings, under normal circumstances, the outlet pressure of lubricating oil is 1.2MPa, the control pressure is low, the jumping value of PSXL-08301 is 0.4MPa, the outlet pressure of lubricating oil pump is low, the setting value of PSXL-08404 is 0.6MPa, the two switches Action pressure is very close, so when the lubricant pump outlet pressure switch a little lag, it is possible to cause the first carbon dioxide compressor jumped, and then start the lubricating oil pump.
Interlock to improve the program and the effect The key to solve this problem is to reduce the low delay of the oil switch lag, start the auxiliary pump in time. To this end we will change the switch setting value from 0.6MPa to 0.8MPa, so not only reduce the lag time since the start switch, but also widened the interlocking jump value and auxiliary pump self-starting value of the distance, basically to avoid Jumping car switch ahead of the phenomenon. After several years of operation proved to be very successful transformation, not only did not appear to start the auxiliary pump lag phenomenon, there has been no sub-pump start frequently.
We cooperate with Shanghai Jiao Tong University to research, develop and manufacture biomass boilers that use wood chips, straws, palm shells, mesocarp fiber, empty fruit bunch (EFB) fiber, rice husk and other wastes as fuels in order to achieve zero carbon dioxide emissions. After numerous tests and simulations, we have developed a reasonable structure of furnace arch, furnace wall and furnace heating surface that guarantees combustion efficiency and evaporation rate. NOx emissions of our biomass boilers can be as low as 100 mg/Nm3 with thermal efficiencies up to 90%.